Central thermostatic mixing valve for water circuits
from 44° to 58°C:
Anti-scalding safety.
Compensates for temperature fluctuations.
Filters and non-return valves are accessible from the outside
without dismantling the mechanism.
Thermal rinsing is possible.
Interchangeable cartridge with self-acting element.
Chrome-plated brass body with high surface hardness.
Maximum hot water temperature: 85°C.
Differential between hot water and mixed water: 15°C min.
Pressure difference at the inlets: 1 bar max (0.5 bar recommended).
Min/max pressure: 1 to 10 bar (1 to 5 bar recommended).
Hot water inlet on the left (red ring) and cold water on the right (blue ring).
Mixed water outlet at the top (purple ring).
Bottom outlet possible: unscrew the plug, reposition it at the top,
and install the mixed water outlet fitting at the bottom.
Protects and extends the service life of the network
(DHW > 65°C = cause of premature aging).
Temperature limiter adjustable by the installer.
Reduces the risk of scalding by lowering the temperature
at the outlet of the hot water production system.
140 l/min - M1"1/4.
30-year warranty
Specifications
| Article number | 8146731054 |
|---|---|
| Brand | Delabie |
| Weight | 3.842 kg |